Sample Data

HVAC Equipment

Chiller

Meter readings and field data collection for a typical chiller.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Evaporator Entering Numeric Temperature     47 53
Evaporator Leaving Water Numeric Temperature     42 44
Condenser Entering Water Numeric Temperature     78 84
Condenser Leaving Water Numeric Temperature     85 90
Evaporator Rfgt Numeric Pressure     -9 -8
Evaporator Approach Numeric Temperature     0 3
Condenser Refrigerant Numeric Pressure     2 5
Condenser Approach Numeric Temperature     0 4
Compressor Number Numeric Starts        
Compressor Running Numeric Time        
Compressor Rfgt Discharge Numeric Temperatures     90 110
Oil Tank Numeric Pressure     -9 -7
Oil Pump Discharge Numeric Pressure     10 18
Oil Differential Numeric Pressure        
Oil Tank 2 Numeric Temperature     105 150
Inboard Bearing #1 Numeric Temperature     90 160
Outboard Bearing #2 Numeric Temperature     90 160
IGV Position Numeric Percent Open        
Motor L1 Numeric Amperages        
Motor L2 Numeric Amperage        
Motor L3 Numeric Amperage        
Motor A/B Numeric Voltage        
Motor B/C Numeric Voltage        
Motor C/A Numeric Voltage        
Power Consumption Numeric Kilo Watts        
Power Factor Numeric Percent        
Motor Windings #1 Numeric Temperature     65 130
Motor Windings #2 Numeric Temperature     65 130
Motor Windings #3 Numeric Temperature     65 130
Purge Mode On, Idle          
Pump Out Life Numeric Minutes        
Purge Liquid Numeric Temperature     85 90
Condenser Water Numeric Delta Pressure     9 14
Chilled Water Numeric Delta Pressure     8 14
Opearting Oil Level OK, Not OK          
Back Up Unit CHP A, CHP B, CHP C, CHP D          
Back Up Unit In Hand, Off, Auto          
Back Up Unit 2 Numeric Oil Temperature     105 150

Air Handler Unit (AHU)

Meter readings and field data collection for a typical AHU.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Frequency Numeric Hertz 0 60 30 45
Current Numeric Amperage        
Load Numeric Percent 0 100    
ATS On Source 1, Source 2          
Test for Unusual Noises or Vibrations Pass, Fail          

 

Condensate Return Unit (CRU)

Meter readings and field data collection for a typical CRU.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Status Cooling, Fan, Heating, Dehumidifying, Humidifying (MULTI SELECT)          
Temperature Numeric Degrees 60 80    
Humidity Numeric Percent 25 70 35 65
Alarms None, Active Alarms          
Test for Unusual Noises or Vibrations Pass, Fail          

 

 

Compressed Air

Air Compressor

Meter readings and field data collection for a typical air compressor.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Power On Dryer Yes, No          
Temperature Indicator Blue, Green, Red          
Inlet Air Pressure Numeric PSI 0 120 75 110
Outlet Air Pressure Numeric PSI 0 120 70 110
Prefilter Pressure drop Indicator Green, Red          
Prefilter Drained Yes, No          
Desiccant Air Dryer Sight Glass Blue, White          
Electric Condensate Drain Test OK, Not OK, Adjusted, Replaced Parts (MULTI SELECT)          
Air Compressor #1 Numeric PSI 0 125    
Air Compressor #1 2 Numeric Hours        
Drained Tank Yes, No          
Oil Level OK, Not OK          
Outlet valve Open, Closed          
Any unusual noises Yes, No          

 

Compressed Air Regulators

Meter readings and field data collection for compressed air regulators.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Low Side A/B Numeric Pressure        
High Side A/B Numeric Pressure        
Low Side C/D Numeric Pressure        
High Side C/D Numeric Pressure        
Any moisture indications Yes, No          

 

Deluge System

Meter readings and field data collection for a typical deluge system.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Air Numeric Pressure        
Water Numeric Pressure        
Solenoids On, Off          
Tamper Switch OK, Not OK          
Flow Switch OK, Not OK          

 

Fire Compressor

Meter readings and field data collection for a typical fire compressor.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Air Numeric Pressure        
Drain Condensation Yes, No          
Outlet Valve Open Yes, No          
Hours Numeric Total        
Test for Unusual Noises or Vibrations Pass, Fail          

 

 

Pumps

Circulating Raw-Water Pump

Meter readings and field data collection for a typical circulating raw water pump.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
VFD Numeric Frequency 0 60    
Suction Numeric Pressure     15 40
Discharge Numeric Pressure     30 55
Test for Unusual Noises or Vibrations Pass, Fail          

 

Domestic Water

Meter readings and field data collection for domestic water.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
North Process Water Numeric Pressure        
South Process Water Numeric Pressure        
North Potable Water Numeric Pressure        
South Potable Water Numeric Pressure        
Upper Riser any leaks Yes, No          
Lower Riser any leaks Yes, No          

 

Trash Pump

Meter readings and field data collection for a typical trash pump.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Discharge Numeric Pressure 0 50    
Pumps Hand, Off, Auto          
Test for Unusual Noises or Vibrations Pass, Fail          

 

 

Electrical

Generator

Meter readings and field data collection for a typical generator.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Run Numeric Hours        
Day Tank Full, 3/4 , 1/2, 1/4, Empty          
Oil Level OK, Not OK          
Water Level OK, Not OK          
Battery Charger Volts Numeric Voltage        
Battery Charger Amps Numeric Amperage        
Any Leaks Yes, No          

Uninterruptible Power Supply (UPS)

Meter readings and field data collection for a typical UPS.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Module Input Numeric Voltage 460 490    
Module Output Numeric Voltage 460 490    
Module KVA Numeric Output        
Module KW Numeric Kilo Watts        
DC Batteries Numeric Voltage        
DC Batteries 2 Numeric Amperage        
Any alarms the last 24 hours Yes, No          

Underground Service Cable (USC)

Meter readings and field data collection for a typical USC.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
System Input Numeric Voltage 460 490    
System Output Numeric Voltage 460 490    
System KVA Numeric Output        
System KW Numeric Kilo Watts        
System Out of Balance Yes, No          
Modules Connected 3 of 3, 2 of 3, 1 of 3          
System Redunancy Redundant, Non Redundant          
Any alarms the last 24 hours Yes, No          
UPS Distribution Panel B Numeric Kilo Watts        

Power Distribution Unit (PDU)

Meter readings and field data collection for a typical PDU.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Primary Input Numeric Voltage 465 495    
Output L/L Numeric Voltage 195 220    
Output L/N Numeric Voltage 105 130    
Output Numeric Kilo Volt Amps        
KW reading Numeric Kilo Watts        
Output 2 Numeric Percent Load        
Any active alarms None, Active Alarms          

Electric Meter

Meter readings and field data collection for a typical electric meter.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Read and record KWH Numeric KWH        
Read and record Max KW Numeric KW        
Read and record KVAR Numeric KVAR        

 

 

Water

Water Meter

Meter readings and field data collection for a typical water meter.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Confined Entry Procedure will be followed. Yes          
Record Meter reading Numeric Cubic Feet        

Daily Water Check

Meter readings and field data collection for a typical daily water check.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
A/B Trasar Numeric PPM     90 110
A/B Conductivity Numeric PPM     2300 2800
C/D Trasar Numeric PPM     90 110
C/D Conductivity Numeric PPM     2300 2800

Weekly Water Test

Meter readings and field data collection for a typical weekly water test.

Item Name
Input Type
Unit
Min
Max
Optimal Min
Optimal Max
Conductivity Numeric Level        
RO Softness Numeric PPM        
RO Total Chlorine Numeric PPM        
Water Meter #1 Numeric Gallons        
Water Meter #2 Numeric Gallons        
Water Meter #3 (CT) Numeric Gallons        
Trasar Level Numeric Gallons        
Starbrex Level Numeric Gallons